Eurofyre Knowledge Base

Dycon EN54 Power Supply

Knowledge Base

Key Features

Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply
  • Intelligent “On-Demand” Load Sharing
  • Advanced Battery Impedance Monitoring
  • Electronic “E-Fuse” Technology
  • Optional Real-Time Performance Monitoring
  • Temperature-Compensated Charging

Overview

The Dycon D234x Series isn’t just a power source; it’s the heart of a dependable fire alarm system. Fully certified to EN54-4:1997 +A1:2002 +A2:2006 and EN54-2, these switch-mode power supply units (PSUs) offer unparalleled reliability for fire detection, voice alarm, and smoke control systems across the UK and Europe.

Why Choose the Dycon D234x Series?

Maintaining a fire system requires precision and maximum uptime. The D234x series is engineered to minimise “nuisance” service calls and protect your battery investment through sophisticated microprocessor control.

Intelligent “On-Demand” Load Sharing
The PSU dynamically shifts power between the system load and battery charging. If the system requires a sudden burst of current, the PSU prioritises the load without compromising the battery health.
Precision Battery Care
By monitoring Battery Impedance rather than just voltage, the unit identifies failing batteries before they cause a system fault. This proactive approach significantly reduces emergency maintenance costs and site visits.
Self-Healing E-Fuse Technology
Forget the hassle of blown glass fuses. Our intelligent electronic fuses (E-Fuses) automatically reset once a fault is cleared, keeping the system online and saving engineers from unnecessary component replacements.
Real-Time Monitoring
Customise your setup with the optional digital display for instant diagnostics—check voltage, current, and resistance at a glance without needing a multimeter.

Turntable

D2431-7 & D2433-7

Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply

D2433-17 & D2435-17

Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply
Dycon D234x EN54-4 Fire Power Supply

Approvals

The Dycon D234x Series is rigorously tested and independently certified to meet the highest European standards for fire detection and fire alarm systems. This ensures full compliance with building regulations and insurance requirements.

  • EN54-4:1997 +A1:2002 +A2:2006: Power supply equipment for fire detection and fire alarm systems.
  • EN54-2: Control and indicating equipment (where applicable to power requirements).
  • CE & UKCA Marked: Fully compliant with all relevant European and UK safety and electromagnetic compatibility (EMC) directives.

Tech Specs

Voltage230Vac +10% -15%; 50Hz ± 15%
Max. AC Input Continuous CurrentD2431: 0.45A
D2433: 0.9A
D2435: 1.5A
Recommended Fused-Spur Input FusesD2431: 250V T1A
D2433: 250V T3.15A
D2435: 250V T3.13A
Output Voltage with AC PowerMinimum: 26Vdc
Maximum: 29.5Vdc Nominal
Output Ripple<0.07V Peak-to-Peak at Full Rated Output
Maximum Output Current at Full LoadD2341: 1.5A
D2343: 3A
D2345: 5A
Battery Charging Voltage & Charging Current27.6Vdc

On-Demand (Maximum)
D2431: 1.5A
D2343: 3A
D2345: 5A
Type of Batteries RequiredD2431-7 & D2433-7:
2 x 12Vdc 7 or 8Ah Sealed Lead Acid Batteries

D2433-17 & D2435-17:
2 x 12Vdc 17Ah Sealed Lead Acid Batteries
Standby Output VoltageMinimum: 21Vdc
Maximum: 27.6Vdc
PSU Standby Current32mA
Over-Voltage Cut-Out Threshold30Vdc 2%
Low-Voltage Power Output Fault<22Vdc ±2% Low Voltage Restore >23Vdc ±2%
Battery Deep Discharge Voltage Limit21Vdc ±2%
Output Monitoring ThresholdBattery Charging Voltage <±2%
Battery Fuse6A PTC Non-replaceable
Fault Opto-Relays3 x Normally Closed (NC) or NO with Jumper Setting, 100mA at 60V

On-Resistance 16 Ohms Maximum

1500VRMS Isolation Voltage

AC Power Fail, Battery Fault, PSU Fault
Operating Temperature Range-10˚C to +40˚C
Humidity95% Non-condensing
Dimensions (W x H x D)D2431-7 & D2433-7:
295mm x 330mm x 90mm

D2433-17 & D2435-17:
379mm x 394mm x 90mm

Downloads

    Contact Eurofyre