  • Detectors, call points, sounders and ancillaries connected to same two wires
  • Addressable radial (zone) or loop wiring
  • Selectable sounder tone (panel selected)
  • Cable break identification
  • Cable short-circuit protection

Learn about the ProFyre T8 2-Wire Fire Alarm Panel in the

Eurofyre Knowledge Base
Part Number: 14-001-P Category: Brand:

Learn about the ProFyre T8 2-Wire Fire Alarm Panel in the

Knowledge Base

Description

The ProFyre T8 2-Wire Fire Alarm Panel provides a versatile solution for small to medium-sized installations, integrating conventional, basic addressable, and 2-wire conventional technologies. Ideal for new builds, retro-fits, and Houses in Multiple Occupation (HMOs), it prioritises ease of installation, wiring flexibility, and reducing unwanted alarms.

The system allows wiring as up to eight radials or a single loop, connecting all detectors, call points, sounders, and interfaces via the same two wires. This design enables two-core spurs and tees within zones and eliminates the need for end-of-line devices or true radial wiring, significantly reducing installation time and costs.

Key functionalities include unique device identification, facilitating easy location of individual components with optional text labels. The panel also offers cable break identification and incorporates short-circuit isolators per radial zone to prevent system disruption. An auto-configuration function verifies connected devices, streamlining commissioning.

For environments like HMOs, the T8 features advanced alarm verification. Smoke detectors can be programmed to trigger a local alarm initially, allowing occupants to address the situation before full evacuation, with a failsafe for heat detection or a second smoke alarm. All devices are constantly monitored, reporting malfunctions with a unique ID and a time-stamped log. A ‘Zone Check’ facility aids in identifying devices and verifying cable runs. Seamless integration with Wi-Fyre wireless technology, via a zone/loop powered interface, allows wireless components to be added without extra power supplies, further enhancing system adaptability.

Additional information

Alarm Identification

Common Identification, Device Identification, Zonal Identification

Application

Agricultural, Commercial, Education, Government, Healthcare, Heritage, Hospitality, Industrial, Information Technology, Leisure, Office, Public Buildings, Residential, Retail, Transport

Battery Capacity

2 x 7Ah

Brand
Cable Entries

15

Colour

White

Country of Origin

United Kingdom

Devices

120, 30, 60

Environment

Indoors

HS Code

8531103000

Input Voltage

230VAC

Loops

1

Mounting

Semi-flush, Surface

Networkable

No

Product

Fire Alarm Control Panel

Programming

On-board

Protocol

Open Protocol

Standards

EN54-2, EN54-4

System

Fire Detection

System Category

Addressable

System Protocol

Zeta MKII

Wiring

Loop, Radial

Zones

2, 4, 8

Relays

2

Detection Architecture

Coincidence, Independent

Unit

Piece

Indication

LCD Display, LED