Eurofyre Knowledge Base

Zeta MKII Addressable Optical Smoke Detector

Knowledge Base

Key Features

Zeta MKII Addressable Optical Smoke Detector
Zeta MKII Addressable Optical Smoke Detector
Zeta MKII Addressable Optical Smoke Detector
  • Addressable optical smoke detection
  • Reliable response to smouldering fires
  • Designed for Zeta MKII systems
  • Low profile detector design
  • Simple installation and maintenance

Overview

The Zeta MKII Addressable Optical Smoke Detector provides reliable smoke detection for use with Zeta MKII addressable fire alarm systems. It uses an optical sensing chamber to detect smoke particles produced by slow-burning or smouldering fires, making it suitable for many commercial and public environments.

The detector communicates directly with the fire alarm control panel through the addressable loop, allowing each device to be individually identified and monitored. This improves fault finding and enables faster response during alarm conditions.

Its low profile design allows discreet installation while maintaining effective detection performance. The detector is designed for straightforward installation, commissioning and maintenance within Zeta MKII fire detection systems.

Turntable

Zeta MKII Addressable Optical Smoke Detector
Zeta MKII Addressable Optical Smoke Detector
Zeta MKII Addressable Optical Smoke Detector

Approvals

The Zeta MKII Addressable Optical Smoke Detector carries LPCB certification and CE marking, demonstrating compliance with recognised fire safety and product performance standards.

Tech Specs

Detector classOptical smoke
Design standardEN54-77
ApprovalLPCB
Operating voltage17 to 28 V DC
Quiescent current500 µA
Alarm current @ 24V DC5 mA
Operating temperature-10 to +50 °C
Min. continuous Temp.0 °C
Max. humidity95% RH non-condensing
Alarm condition0.09 dB/m to 0.11 dB/m
Coverage100 m²
IP ratingIP43
Start-up time10 Seconds
Size (with base)100 x 49 mm
Weight (with base)75 g (133 g)
Remote output5 mA at 24 V DC