Key Features
- Two-wire design reduces installation time and cost
- Identifies each device for precise monitoring and maintenance
- Compatible with iOS and Android via the ID2 Smartphone App
- Cable break and short-circuit protection for enhanced reliability
- Complies with EN54 Parts 2 and 4 and BS 5839 Parts 1 and 6
Overview
The Infinity ID2 2-Wire Addressable Fire Alarm Panel combines the simplicity of conventional wiring with the intelligence of addressable control. Designed to meet EN54 Parts 2 and 4, it supports up to 15 devices per zone and is available in 2, 4 or 8-zone models. Devices share a single two-core cable, reducing wiring time and cost while maintaining full device identification and control.
Built on Zeta’s proven communication protocol, the ID2 offers easy installation, fast commissioning and reliable performance. It includes event logging, alarm verification and full device status monitoring. The system can be used for new installations or as an upgrade for existing two-wire or conventional systems without re-cabling.

The 2 Zone/1 Loop Addressable Fire Alarm Panel offers intelligent, reliable detection for small installations, supporting up to 250 devices with flexible programming and easy operation.

The 4 Zone/1 Loop Addressable Fire Alarm Panel offers enhanced capacity for medium-sized buildings. It supports up to 250 addressable devices, providing flexible programming, clear status indication and reliable fire detection. Its user-friendly interface and robust performance make it ideal for offices, schools and residential complexes.

The 8 Zone/1 Loop Addressable Fire Alarm Panel provides advanced protection for larger buildings. It supports up to 250 addressable devices, offering full cause-and-effect programming, event logging and intuitive control. Designed for reliability and ease-of-use, it ensures comprehensive monitoring across multiple zones within a single system.
Turntable



Approvals


Tech Specs
| Supply Voltage | 230V AC +10% /- 15% @ 50/60 Hz |
| System Voltage | 29V DC Nominal (19 – 30 V) |
| Sounder Output | Loop Powered Sounders2 x Conventional Sounder Circuits28V Nominal, 150mA (20-30V DC) |
| Fault Output | 1 x Fault Relay SELV@1A (Normally Energised) |
| Fire Output | 1 x Fire Relay SELV@1A |
| No. of Zones | 2, 4, or 8 |
| Zone Capacity | 15 Devices per Zone |
| Max. No. of Detection Circuits | Radial Mode – 8 Radial CircuitsLoop Mode – 1 Loop Circuit |
| Max. Loop Sounder Quantity | 80 Sounders |
| Repeater Connection | RS485 |
| Dimensions (W x H x D) | 370 x 311 x 113mm |