Understanding EN 54-20 Aspirating Smoke Detection Sensitivity Classes

3 mins read

Aspiraiting Smoke Detection Class Sensitivity Table

EN 54-20 specifies 3 classes of sensitivity to help with the vast amount of applications aspirating smoke detection can be used for. This is to ensure that the most appropriate sensitivity aspirating smoke detector will be selected for the proposed application/area.

Server Room

Class A – Very High Sensitivity

For the earliest indication of smoke so that early measures can be initiated before any significant damage is incurred in areas containing high value, critical or strategically important artefacts or operations such as data centres.
Atrium

Class B – Enhanced Sensitivity

Enhanced sensitivity for effective early detection in challenging environments or within critical equipment e.g. to combat smoke dilution where there are high air flow or where the ceiling is higher than normal.
Office

Class C – Normal Sensitivity

As an alternative to point or beam type smoke detectors (normal sensitivity) for a variety of physical reasons e.g. maintenance access, building deflection, dilution of smoke, and obstructions to line of sight such as cold stores and warehouse facilities.

Eurofyre are the technical suppliers for the extensive range Xtralis ICAM aspirating smoke detection products. Many of which can be configured to class A, B and C sensitivity. Below are a few examples from the large bore ASD category.

 
EF-FT1 Aspiraiting Smoke Detector

EF-FT1 – High Sensitivity Aspirating Smoke Detector

  • Class A – 16 Holes / 0.04% obs/m
  • Class B – 72 Holes / 0.04% obs/m
  • Class C – 72 Holes / 0.10% obs/m
EF-FTP Aspiraiting Smoke Detector

EF-FTP – High Sensitivity Aspirating Smoke Detector

  • Class A – 12 Holes / 0.04% obs/m
  • Class B – 36 Holes / 0.04% obs/m
  • Class C – 36 Holes / 0.10% obs/m
EF-LASD Aspiraiting Smoke Detector

EF-LASD – High Sensitivity Aspirating Smoke Detector

  • Class A – 3 Holes
  • Class B – 6 Holes
  • Class C – 18 Holes
Xtralis XCC Aspiraiting Smoke Detector

Xtralis XCC – Class C Aspirating Smoke Detector

  • Class C – 18 Holes

    Contact Eurofyre

    SecuriSmoke ASD 2000 for Warehouses

    30th April 2026

    SecuriSmoke ASD 2000 for Warehouses

    Warehouses are essential facilities in supply chains, used to store goods before they are distributed. These large buildings support retail, logistics and manufacturing operations, often holding high volumes of stock in racking systems designed to maximise space. Many modern warehouses also function as fulfilment centres, where goods are received, sorted, picked, packed and dispatched quickly […]

    Read Article
    FyreLine Resettable Linear Heat Detection for Tunnels

    24th April 2026

    FyreLine Resettable Linear Heat Detection for Tunnels

    Road tunnels are critical transport links that support daily travel and economic activity. They often carry high volumes of traffic through enclosed environments where ventilation is limited. Fire detection in tunnels is essential to protect road users, minimise disruption, and support safe evacuation and emergency response. Early and reliable detection allows operators to respond quickly, […]

    Read Article
    • FyreLine Linear Heat detection
    • Crisis Emergency Voice Communication
    • Xenos Wireless Fire Detection

    Eurofyre is proud to supply its own brands to the fire detection and safety market. All of our products are high quality, extremely reliable and cost-effective.

    Sales & Technical Support

    Eurofyre Sales and Technical Support

    Accreditations

    ISO 9001
    UKAS Management System
    Fire Industry Association
    British Chamber of Commerce