Key Features
- Supports up to 32 devices per zone
- One-man test and zone disablement functions
- Optional metal back box for larger batteries
- 2 or 4 configurable sounder circuits with delay option
- EN54-2 and EN54-4 certified for reliability and compliance
Overview
The Infinity 8 Conventional Fire Alarm Panel is a reliable, cost-effective control panel designed for small to medium installations. Available in 1, 2, 4, 6 and 8-zone models, it supports up to 32 devices per zone and includes two or four sounder circuits depending on model. The panel features a modern flame-retardant ABS enclosure with a fully removable front cover for easy wiring access, and can also be supplied with a metal back box for larger 7Ah batteries.
The Infinity 8 offers essential features such as one-man test, zone and sounder disablement, sounder delay options and password access to eliminate lost key issues. With full compliance to EN54 Parts 2 and 4, the Infinity 8 delivers dependable performance and straightforward operation for schools, offices, shops and small residential blocks.

The 1 Zone Infinity 8 Panel provides simple, reliable fire detection for small premises, supporting up to 32 devices on a single zone.

The 2 Zone Infinity 8 Panel offers dependable fire detection for small buildings, supporting up to 64 devices across two zones with simple setup and control.

The 4 Zone Infinity 8 Panel provides reliable fire protection for medium sites, supporting up to 128 devices with four zones and independent sounder control.

The 6 Zone Infinity 8 Panel delivers efficient fire detection for larger installations, supporting up to 192 devices with flexible configuration and clear zone indication.

The 6 Zone Infinity 8 Panel delivers efficient fire detection for larger installations, supporting up to 192 devices with flexible configuration and clear zone indication.

The 8 Zone Infinity 8 Panel offers comprehensive fire detection for large buildings, supporting up to 256 devices with full zone control and easy maintenance access.
Turntable



Approvals


Tech Specs
| Mains Voltage | 230v AC +10% / -15% @ 50/60 Hz |
| System Voltage | 24v DC (Nominal) |
| Zone Voltage | 21v DC (Nominal) |
| Sounder Alarm Output | 2 X 150mA @ 24v DC, 4 X 150mA @ 24v DC |
| Fault Relay | 1 X Volt Free Relay, Selv @ 1A Max |
| Zone Capacity | 32 Devices Per Zone |
| Remote sounder operation | Via N/O Contact Connected To Class Change |
| Sounder Activation Delay | 0 To 10 Minutes In 1 Minute Increments |
| Zone End of line | 1n4002 Diode (Cathode Stripe To Zone +Ve) |
| Sounder End of Line | 10K Resistor |
| Charger Voltage | 27.6V |
| Battery cut off | Battery Voltage Less Than 20V |
| Battery Internal Resistance limit | 0.9 ohm |
| Enclosure size (W x D x H) | 371 X 302 X 93mm |
| Weight | 3 kg (Excluding Batteries) |
| Maximum battery space | 2 X 3.4 Ah, 12V DC Sealed Lead Acid |