Key Features
- IP66 rated for outdoor and harsh environments
- Combined sounder and visual alarm
- Loop powered with up to 200 devices per loop
- Adjustable sound output via infrared remote
- Active monitoring of sounder and VAD circuits
Overview
The SenTRI EP IP66 Sounder & VAD is an addressable fire alarm notification device combining high-power audible signals with a certified visual alarm beacon (VAD) in one unit. It supports loop-powered operation with no separate supply needed. The unit features full compliance with EN54-3 (sounder) and EN54-23 (VAD) standards and offers an IP66 ingress protection rating for demanding or outdoor environments.
The visual flash colour is available in red or white, while the body is red. The device actively monitors both the sounder and VAD circuits to ensure ongoing integrity and signalling reliability.
This combined device is ideal for both indoor and harsher external or industrial areas where high reliability, minimal maintenance and clear occupant notification are required.
Turntable



Approvals



Tech Specs
| Strobe Colour | Red or White | ||
| Approx Max Quantity per Loop(Dependent On Loop Load) | High Power – 38Medium Power – 47Low Power – 72 | ||
| Ingress Protection EP Range | IP66 | ||
| Approx Weight | 0.3 Kg | ||
| Operating Temperature | -10°C to +50°C | ||
| Sound Output at 1m | 103 dB(A) ± 3 dB(A) | ||
| Power Setting | High | Medium | Low |
| Red | W-6.7-14 | W-6.5-12.5 | W-5-9.5 |
| White | W-5-12.5 | W-4.5-11.3 | W-3-8.5 |
| VAD Category –Standard Performance* | Red and White Units W3-8.5 | ||
| VAD Flash Frequency | 0.5 Hz | ||
| Approvals | Sounder VAD EN54-3, EN54-23:2010, EN54-17 | ||